Difference between revisions of "Common Problems"
From PREX Wiki
Jump to navigationJump to search (Created page with "== Problems and Solutions == *") |
|||
Line 1: | Line 1: | ||
== Problems and Solutions == | == Problems and Solutions == | ||
− | * | + | *Collimator Temperature is Rising |
+ | **If the collimator temperature alarm goes off, call MCC and tell them to turn off the beam. Then call the RC. | ||
+ | **Don't raise the temperature alarm limits on the collimator. If it's getting warm, something's wrong | ||
+ | **Things to check: | ||
+ | ***Is the collimator cooling? Stripchart should show 5 for the water flow at all times. | ||
+ | ***Is the raster size correct? Correct size is written on white board. | ||
+ | ***Have the Raster quads (Moller quads) been set to the correct values? See strip chart called "RasterQuadsCheck" and scale back in time to look for changes to values | ||
+ | ***Are the bpms working? IPM1H04A and IPM1H04E XPOS and YPOS should read out nonzero numbers on the strip chart when beam is on. | ||
+ | ***Is the beam in the right position? See appropriate IPM1H04A and IPM1H04E XPOS and YPOS written on the whiteboard. | ||
+ | ***Is the HallATGT lock enabled? Call MCC and ask if the target lock is enabled |
Revision as of 09:31, 30 July 2019
Problems and Solutions
- Collimator Temperature is Rising
- If the collimator temperature alarm goes off, call MCC and tell them to turn off the beam. Then call the RC.
- Don't raise the temperature alarm limits on the collimator. If it's getting warm, something's wrong
- Things to check:
- Is the collimator cooling? Stripchart should show 5 for the water flow at all times.
- Is the raster size correct? Correct size is written on white board.
- Have the Raster quads (Moller quads) been set to the correct values? See strip chart called "RasterQuadsCheck" and scale back in time to look for changes to values
- Are the bpms working? IPM1H04A and IPM1H04E XPOS and YPOS should read out nonzero numbers on the strip chart when beam is on.
- Is the beam in the right position? See appropriate IPM1H04A and IPM1H04E XPOS and YPOS written on the whiteboard.
- Is the HallATGT lock enabled? Call MCC and ask if the target lock is enabled