− | = | + | = Hall A/Target Alarm Handler = |
[[File:hacweb7tools.png|thumb|600px|right|Figure 1 - Click on the red toolbox in the lower left of the hacweb7 screen (4th icon from the left).]] | [[File:hacweb7tools.png|thumb|600px|right|Figure 1 - Click on the red toolbox in the lower left of the hacweb7 screen (4th icon from the left).]] | ||
Line 15: | Line 15: | ||
[[File:Alarm_handler_open.png|thumb|600px|right|Figure 3 - The window that opens when you click on the alarm handler button. There is a red alarm]] | [[File:Alarm_handler_open.png|thumb|600px|right|Figure 3 - The window that opens when you click on the alarm handler button. There is a red alarm]] | ||
− | == Start a new instance of the | + | == Start a new instance of the Hall A Alarm handler == |
− | * | + | * From the EPICS control computer (hacweb7), click on the red toolbox in the lower left corner (see Figure 1) |
− | * Click on ''"AlarmHandler"'' | + | * Click on '''"AlarmHandler"''' in the popup menu |
* The window shown in Figure 2 should appear | * The window shown in Figure 2 should appear | ||
* Move the alarm handler window to the upper right of the screen | * Move the alarm handler window to the upper right of the screen | ||
* Pin the window to all of the desktops | * Pin the window to all of the desktops | ||
− | ** Click on the ''"AlarmHandler"'' in the upper left corner | + | ** Click on the '''"AlarmHandler"''' in the upper left corner |
− | ** Mouse over ''"To Desktop"'' | + | ** Mouse over '''"To Desktop"''' |
− | ** Choose ''"All Desktops"'' at the top of the drop down menu | + | ** Choose '''"All Desktops"''' at the top of the drop down menu |
+ | * Open the Current Alarm History | ||
+ | ** Click the '''"View"''' context menu and select '''"Current Alarm History Window"''' | ||
+ | ** This is most useful for getting detailed information about timing and values of alarms as they accumulate | ||
+ | * If an alarm is white then it is a communications failure from an EPICS Input/Output controller (IOC) and should rectify itself in a minute or less (otherwise call the RC) | ||
+ | * If an alarm is red it means that some important parameter is out of range | ||
+ | ** Please keep track of the set points and current value of anything that alarms, and if the alarm isn't transient and trivial please make a HALOG entry about it | ||
+ | ** If the alarm continues for more than a few seconds please try to understand the nature of the issue and contact the RC or other nearby experts if it isn't immediately clear how to resolve it | ||
+ | |||
+ | == Start a new instance of the Target Alarm Handler == | ||
+ | |||
+ | * Make sure the target gui is running on the poltarac computer | ||
+ | cd ~/Desktop/PRex | ||
+ | ./tgtgui | ||
+ | Select the ALARMS button | ||
+ | * It should be similar to the Hall A alarm handler, but with difference tracked EPICS variables | ||
== Responding to an alarm == | == Responding to an alarm == |
Revision as of 19:16, 23 June 2019
In the process of editing and updating this page. Please contact Juliette Mammei crowder@jlab.org with questions or suggestions.
PREX Main<< Information for Shift Takers << Shift Leader
Experimental Python Alarm Handler
The new python alarm handler lives (for now) in a SBU JLab GitHub Repository
Start a new instance
From within the apar account, execute the ~/bin/ command
AlarmHandler
Hall A/Target Alarm Handler
Start a new instance of the Hall A Alarm handler
- From the EPICS control computer (hacweb7), click on the red toolbox in the lower left corner (see Figure 1)
- Click on "AlarmHandler" in the popup menu
- The window shown in Figure 2 should appear
- Move the alarm handler window to the upper right of the screen
- Pin the window to all of the desktops
- Click on the "AlarmHandler" in the upper left corner
- Mouse over "To Desktop"
- Choose "All Desktops" at the top of the drop down menu
- Open the Current Alarm History
- Click the "View" context menu and select "Current Alarm History Window"
- This is most useful for getting detailed information about timing and values of alarms as they accumulate
- If an alarm is white then it is a communications failure from an EPICS Input/Output controller (IOC) and should rectify itself in a minute or less (otherwise call the RC)
- If an alarm is red it means that some important parameter is out of range
- Please keep track of the set points and current value of anything that alarms, and if the alarm isn't transient and trivial please make a HALOG entry about it
- If the alarm continues for more than a few seconds please try to understand the nature of the issue and contact the RC or other nearby experts if it isn't immediately clear how to resolve it
Start a new instance of the Target Alarm Handler
- Make sure the target gui is running on the poltarac computer
cd ~/Desktop/PRex ./tgtgui Select the ALARMS button
- It should be similar to the Hall A alarm handler, but with difference tracked EPICS variables
Responding to an alarm
- Click on the alarm handler window in the upper right of the hacweb7 monitor (see Figure 2)
- This will open a window that lists the various pieces of equipmen (see Figure 3)